Former deputy chief executive admitted he was not sure if the decision was permitted under UK fire regulations

A major certifying body may have based the fire rating it gave a combustible insulation product which was used on the refurbishment of Grenfell Tower on tests of different products, the inquiry has heard.

The former deputy chief executive at the British Board of Agr茅ment (BBA), Brian Moore, admitted it was 鈥渕ore likely than not鈥 that the classification of Kingspan鈥檚 K15 insulation had been 鈥渆xtrapolated鈥 from test reports on other phenolic foam products produced by the firm dating back as far as 1991.

Moore, who joined the BBA in 2014, told Tuesday鈥檚 hearing that there were no records of test data being received by Kingspan in the folder of a 2008 certificate which gave the product a Class 0 rating, with the folder鈥檚 fire section instead containing a series of fire reports on other Kingspan products.

The certificate stated that K15, a combustible phenolic foam material, 鈥渨ill not contribute to the development stages of a fire or present a smoke or toxic hazard鈥.

Brian Moore 1

Brian Moore giving evidence to Tuesday鈥檚 hearing

In fact, the inquiry has already heard that a fire test on K15 conducted a year before the BBA certificate was issued had turned a test rig into a 鈥渞aging inferno鈥 that had to be extinguished out of fears that it would endanger the laboratory.

Inquiry counsel Richard Millett QC asked: 鈥淒o you agree with me that if K15 is indeed, as I think you have accepted, a combustible material, the statement, 鈥橳he boards will not contribute to the development stages of a fire鈥 is inaccurate and misleading?鈥

Moore replied: 鈥淚f Kingspan K15 will burn, and will contribute to the development stages of a fire, then that is not correct.鈥

He added that while it was 鈥渘ot unusual for the BBA to extrapolate its opinion from one product to a similar one,鈥 he said that he 鈥渃an鈥檛 be certain whether that is permitted鈥 under UK fire regulations.

Millett then asked if the BBA followed any particular guidance when carrying out the extrapolations.

Moore replied: 鈥淕uidance? Not that I鈥檓 aware of. It would be the opinion鈥 the technical opinion of the competent individual, supported by their peers.鈥

He added: 鈥滱 lot of the BBA work is a technical opinion, which we need to stand by in evidence, but I鈥檓 not aware that there鈥檚 specific guidance in this case that was applied in terms of making the decision about extrapolation, if indeed that was the case.鈥

The inquiry was shown a summary of the test reports which the BBA used to give the foil-faced K15 a Class 0 rating, showing a variety of different types of phenolic foam products.

Millett asked if Moore knew what consideration was given to the fact that none of these products appeared to have the same facer arrangement as K15 at the time of the certificate

The earliest test, from 1991, was of a product which was unfaced. A report from 1993 was of a product which used a glass tissue backing and an aluminium facing, with another test from the same year using just glass tissue. Two more tests from 2003 were of products which used both aluminium and glass tissue facers.

Millett asked if Moore knew what consideration was given to the fact that none of these products appeared to have the same facer arrangement as K15 at the time of the certificate.

Moore replied: 鈥淚f they were in the folder, in the section that related to fire, then it was the assumption, the belief, that they had been considered.鈥

He added: 鈥淣ow, whether that鈥 whether they were satisfactory evidence to make the opinion that would support BS 476 [British fire standards] in the absence of a test, I can鈥檛 comment. If they鈥檙e not sufficiently similar, then that can鈥檛 be a good thing.鈥

Asked how similar products have to be for the data to be extrapolated, Moore said that he did not know and admitted that he had not checked or discussed either the concept or the methodology of extrapolation of test data with a fire engineer.

Millett then asked if Moore could explain why the BBA had not simply followed up to Kingspan with a specific request for fire test data. Moore said he could not, adding: 鈥淚t does seem to me it would be easier just to ask for the fire test.鈥

Asked if issuing the certificate in the absence of test data 鈥 which, if supplied, would have shown that K15 fell far short of achieving Class 0 鈥 was a 鈥渧ery basic failure of due diligence on the part of the BBA鈥, Moore answered: 鈥淚f there was no basis upon which to include that statement in the certificate, then that can鈥檛 be correct, that can鈥檛 be right.鈥

The inquiry has already heard how Kingspan had changed the chemical composition of its K15 product a year after it had passed a 2005 fire test but had continued to use the test results from the older version of the product to market the newer version as safe for use on buildings above 18m.

In a letter sent to the 好色先生TV Research Establishment last year, Kingspan said it was 鈥渘ow of the view鈥 that the product it had been selling to the market since 2006 was different to what had been tested.

Last month, the BBA announced proposals to begin unannounced testing of randomly selected materials which are already being sold on the market.

It also said that it wanted to have earlier involvement with manufacturers during their product development process, including observation of tests submitted for assessment, reviews of all test results and storage of samples of materials used in tests for future reference.

K15 was never specified for the refurbishment of Grenfell Tower but was found to be included in the building鈥檚 cladding system after the disastrous fire which killed 72 people in June 2017.

The first phase of the inquiry into the fire has already found that the insulation products included in the cladding system 鈥渕ore likely than not鈥 contributed to the spread of flames up the side of the tower. 

The inquiry continues.